P R O D U C T S
 

 

 

Comparative tables

KV Bil 12 25 35 40 50 80 90
 
SERIE G   G2 G3   G5 G10 G15
SERIE GN       GN65     GN140
SERIE BT BT4   BT24 BT30 BT36    

 

KV Bil 35 40 60 75 95 125 170 200 250
 
SERIE DC DC
10
DC
15
DC
160
DC
200
DC
260
DC
300
     
SERIE S       S1 S2 S3 S4    
SERIE C     C1 C2 C3 C4 C5 C6  
SERIE E         E1 E2 E3 E4 E6
SERIE SR       CSR
12
    CSR
24
   


MINIMUM NOMINAL CREE PAGE DISTANCES (EN60137)

Level of air pollution

 

I
light

II
medium

III
heavy

IV
very heavy

Max rated voltage (kV)

Total creepage (mm.)

3,6

58

72

90

112

7,2

115

144

180

223

11

176

220

275

341

12

192

240

300

372

15

240

300

375

465

17,5

280

350

438

543

22

352

440

550

682

24

384

480

600

744

36

576

720

900

1116

48

768

960

1200

1488

 

 

 

Note to the Purchaser:
All information provided in this website, including technical specifications and recommendations, is based on the results of tests carried out. However, no guarantee is provided with regard to the fact that information supplied is also entirely accurate and complete. It is in the Purchaser’s interest to verify product compatibility with the use intended. All products sold by Zamber are compliant with Zamber’s in-house standards. Zamber is not liable for any possible after sale damage.